docs: Ported Design Doc to OpenBMC
This is a port of the original Google Design Document for Swampd, now
phosphor-pid-control. This document needs updates to match the latest
changes pertaining to dbus configuration.
Change-Id: Idcef393d06547b108655d08236b1949c04b7367b
Signed-off-by: Patrick Venture <venture@google.com>
| -rw-r--r-- | README.md | 320 | ||||
| -rw-r--r-- | swampd_diagram.png | bin | 0 -> 19942 bytes |
2 files changed, 319 insertions, 1 deletions
@@ -1 +1,319 @@ -# phosphor-pid-control
\ No newline at end of file +# phosphor-pid-control + +[TOC] + +## Objective {#objective} + +Develop a tray level fan control system that will use exhaust temperature and +other machine temperature information to control fan speeds in order to keep +machines within acceptable operating conditions. + +Effectively porting the Chromium EC thermal code to run on the BMC and use the +OpenBMC dbus namespace and IPMI commands. + +## Background {#background} + +Recent server systems come with a general secondary processing system attached +for the purpose of monitoring and control, generally referred to as a BMC[^2]. +There is a large effort to develop an open source framework for writing +applications and control systems that will run on the BMC, known as +OpenBMC[^3]<sup>,</sup>[^4]. Within Google the effort has been internalized +(while also providing upstream pushes) as gBMC[^5]. The primary goal of OpenBMC +is to provide support for remote and local system management through a REST +interface, and also through IPMI[^6] tied together via the system dbus. OpenBMC +provides many applications and daemons that we can leverage and improve. + +The BMC is wired such that it has direct access and control over many +motherboard components, including fans and temperature sensors[^7]. Therefore, +it is an ideal location to run a thermal control loop, similar to the EC. +However, to upstream it will need to follow (as best as possible) the OpenBMC +specifications for communicating and executing[^8]. + +IPMI allows for OEM commands to provide custom information flow or system +control with a BMC. OEM commands are already lined up for certain other accesses +routed through the BMC, and can be upstreamed for others to use. + +## Overview {#overview} + +The BMC will run a daemon that controls the fans by pre-defined zones. The +application will use thermal control, such that each defined zone is kept +within a range and adjusted based on thermal information provided from locally +readable sensors as well as host-provided information over an IPMI OEM +command. + +A system (or tray) will be broken out into one or more zones, specified via +configuration files or dbus. Each zone will contain at least one fan and at +least one temperature sensor and some device margins. The sensor data can +be provided via sysfs, dbus, or through IPMI. In either case, default margins +should be provided in case of failure or other unknown situation. + +The system will run a control loop for each zone with the attempt to maintain +the temperature within that zone within the margin for the devices specified. + +## Detailed Design {#detailed-design} + +The software will run as a multi-threaded daemon that runs a control loop for +each zone, and has a master thread which listens for dbus messages. Each zone +will require at least one fan that it exclusively controls, however, zones can + share temperature sensors. + + + +In this figure the communications channels between swampd and ipmid and +phosphor-hwmon are laid out. + +### OpenBMC Upstream {#openbmc-upstream} + +To be upstreamed to OpenBMC for use on open-power systems, we need to follow the +OpenBMC code style specification[^9] and leverage the dbus framework for reading +sensors and fan control[^10]. + +There is already a daemon, which given a configuration file for a hwmon device, +will add it to the dbus objects namespace which handles queries for values such +a temperature or fan speed and allows another process to control the fan +speed[^11]. It is the goal to utilize this other daemon through dbus to read the +onboard sensors and control the fans. + +Because of the present implementation of the dbus interfaces to require +controlling the fans only via specifying the RPM target, whereas the driver +we're using for Quanta-Q71l (the first system) only allows writing PWM. This +can be controlled either directly or via dbus. + +### Zone Specification {#zone-specification} + +A configuration file will need to exist for each board, likely in YAML[^12]. +Similar information will also be necessary for gsys, such that it knows what +sensors to read and send to the BMC. Presently it does something similar with +EC, so it shouldn't be unreasonable to do something similar. + +Each zone must have at least one fan that it exclusively controls. Each zone +must have at least one temperature sensor, but they may be shared. + +The external devices specified in the zone must have default information as a +fallback, while their current temperatures will be provided by gsys. Some +devices adapt quickly and others slowly, and this distinction will need to be a +factor and described in the configuration. + +The internal thermometers specified will be read via sysfs. + +#### A proposed configuration file: {#a-proposed-configuration-file} + +``` +{ZONEID}: + {PIDID}: + type: "fan" | "margin" + ipmi: + {IPMI_ID} + name: "fan1" + readpath: "/xyz/openbmc_project/sensors/fan_tach/fan1" + writepath: "/sys/class/hwmon/hwmon0/pwm0" + pidinfo: + samplerate: 0.1 // sample time in seconds + p_coeff: 0.01 // coefficient for proportional + i_coeff: 0.001 // coefficient for integral + integral_limit: + min: 0 + max: 100 + output_limit: + min: 0 + max: 100 + slew_negative: 0 + slew_positive: 0 + {PIDID}: + type: "margin" + ipmi: + {IPMI_ID} + name: "sluggish0" + readpath: "/xyz/openbmc_project/sensors/external/sluggish0" + writepath: "" + pidinfo: + samplerate: 1 // sample time in seconds + p_coeff: 94.0 + i_coeff: 2.0 + integral_limit: + min: 3000 + max: 10000 + output_limit: + min: 3000 + max: 10000 + slew_negative: 0 + slew_positive: 0 +``` + +### Chassis Delta {#chassis-delta} + +Due to data center requirements, the delta between the outgoing air temperature +and the environmental air temperature must be no greater than 15C. + +### IPMI Command Specification {#ipmi-command-specification} + +Gsys needs the ability to send to the BMC, the margin information on the devices +that it knows how to read that the BMC cannot. There is no command in IPMI that +currently supports this use-case, therefore it will be added as an OEM command. + +The state of the BMC readable temperature sensors can be read through normal +IPMI commands and is already supported. + +#### OEM Set Control {#oem-set-control} + +Gsys needs to be able to set the control of the thermal system to either +automatic or manual. When manual, the daemon will effectively wait to be told to +be put back in automatic mode. It is expected in this manual mode that something +will be controlling the fans via the other commands. + +Manual mode is controlled by zone through the following OEM command: + +##### Request + +Byte | Purpose | Value +---- | ------------ | ----------------------------------------------------- +`00` | `netfn` | `0x2e` +`01` | `command` | `0x04 (also using manual command)` +`02` | `oem1` | `0xcf` +`03` | `oem2` | `0xc2` +`04` | `padding` | `0x00` +`05` | `SubCommand` | `Get or Set. Get == 0, Set == 1` +`06` | `ZoneId` | +`07` | `Mode` | `If Set, Value 1 == Manual Mode, 0 == Automatic Mode` + +##### Response + +Byte | Purpose | Value +---- | --------- | ----------------------------------------------------- +`02` | `oem1` | `0xcf` +`03` | `oem2` | `0xc2` +`04` | `padding` | `0x00` +`07` | `Mode` | `If Set, Value 1 == Manual Mode, 0 == Automatic Mode` + +#### OEM Get Failsafe Mode {#oem-get-failsafe-mode} + +Gbmctool needs to be able to read back whether a zone is in failsafe mode. This +setting is read-only because it's dynamically determined within Swampd per zone. + +Byte | Purpose | Value +---- | ------------ | ---------------------------------- +`00` | `netfn` | `0x2e` +`01` | `command` | `0x04 (also using manual command)` +`02` | `oem1` | `0xcf` +`03` | `oem2` | `0xc2` +`04` | `padding` | `0x00` +`05` | `SubCommand` | `Get == 2` +`06` | `ZoneId` | + +##### Response + +Byte | Purpose | Value +---- | ---------- | ----------------------------------------------- +`02` | `oem1` | `0xcf` +`03` | `oem2` | `0xc2` +`04` | `padding` | `0x00` +`07` | `failsafe` | `1 == in Failsafe Mode, 0 not in failsafe mode` + +#### Set Sensor Value {#set-sensor-value} + +Gsys needs to update the thermal controller with information not necessarily +available to the BMC. This will comprise of a list of temperature (or margin?) +sensors that are updated by the set sensor command. Because they don't represent +real sensors in the system, the set sensor handler can simply broadcast the +update as a properties update on dbus when it receives the command over IPMI. + +#### Set Fan PWM {#set-fan-pwm} + +Gsys can override a specific fan's PWM when we implement the set sensor IPMI +command pathway. + +#### Get Fan Tach {#get-fan-tach} + +Gsys can read fan_tach through the normal IPMI interface presently exported for +sensors. + +### Sensor Update Loop {#sensor-update-loop} + +The plan is to listen for fan_tach updates for each fan in a background thread. +This will receive an update from phosphor-hwmon each time it updates any sensor +it cares about. + +By default phosphor-hwmon reads each sensor in turn and then sleeps for 1 +second. We'll be updating phosphor-hwmon to sleep for a shorter period -- how +short though is still TBD. We'll also be updating phosphor-hwmon to support pwm +as a target. + +### Thermal Control Loops {#thermal-control-loops} + +Each zone will require a control loop that monitors the associated thermals and +controls the fan(s). The EC PID loop is designed to hit the fans 10 times per +second to drive them to the desired value and read the sensors once per second. +We'll be receiving sensor updates with such regularly, however, at present it +takes ~0.13s to read all 8 fans. Which can't be read constantly without bringing +the system to its knees -- in that all CPU cycles would be spent reading the +fans. TBD on how frequently we'll be reading the fan sensors and the impact this +will have. + +### Main Thread {#main-thread} + +The main thread will manage the other threads, and process the initial +configuration files. It will also register a dbus handler for the OEM message. + +### Enabling Logging + +By default, swampd isn't compiled to log information. To compile it for tuning, +you'll need to add: + +``` +EXTRA_OEMAKE_append_YOUR_MACHINE = " CXXFLAGS='${CXXFLAGS} -D__TUNING_LOGGING__'" +``` + +To the recipe. + +## Project Information {#project-information} + +This project is designed to be a daemon running within the OpenBMC environment. +It will use a well-defined configuration file to control the temperature of the +tray components to keep them within operating conditions. It will require +coordinate with gsys and OpenBMC. Providing a host-side service upstream to talk +to the BMC is beyond the scope of this project. + +## Security Considerations {#security-considerations} + +A rogue client on the host could send invalid thermal information causing +physical damage to the system. There will be an effort to sanity check all input +from gsys to alleviate this concern. + +## Privacy Considerations {#privacy-considerations} + +This device holds no user data, however, you could profile the types of jobs +executed on the server by watching its temperatures. + +## Testing Plan {#testing-plan} + +Testing individual code logic will be handled through unit-tests, however some +pieces of code rely on abstractions such that we can swap out dbus with +something encapsulated such that testing can be done without strictly running on +a real system. + +Testing the system on real hardware will be performed to verify: + +1. The fallback values are used when gsys isn't reporting. +1. The system behaves as expected given the information it reads. + +Unit-tests will provide that we know it validates information from gsys properly +as well as handles difficult to reproduce edge cases. + +The testing of this project on real hardware can likely fold into the general +gBMC testing planned. + +## Notes + +[^2]: BMC - Board Management Controller +[^3]: with url https://github.com/openbmc/openbmc +[^4]: with url https://github.com/facebook/openbmc +[^5]: with url http://go/gbmc +[^6]: with url + http://www.intel.com/content/www/us/en/servers/ipmi/ipmi-second-gen-interface-spec-v2-rev1-1.html +[^7]: Excluding temperature sensors on PCIe cards and other add-ons. +[^8]: They prefer c++. +[^9]: With url + https://github.com/openbmc/docs/blob/master/cpp-style-and-conventions.md +[^10]: with url https://github.com/openbmc/phosphor-dbus-interfaces +[^11]: with url https://github.com/openbmc/phosphor-hwmon +[^12]: YAML appears to be the configuration language of choice for OpenBMC. diff --git a/swampd_diagram.png b/swampd_diagram.png Binary files differnew file mode 100644 index 0000000..39010fb --- /dev/null +++ b/swampd_diagram.png |